Woodward 9907-162 505E Digital Governor for Extraction Steam Turbines
General info
Manufacture | Woodward |
Item No | 9907-162 |
Article number | 9907-162 |
Series | 505E Digital Governer |
Origin | United States(US) |
Dimension | 85*11*110(mm) |
Weight | 1.8 kg |
Customs Tariff Number | 85389091 |
Type | 505E Digital Governor |
Detailed data
Woodward 9907-162 505E Digital Governor for Extraction Steam Turbines
Keypad and Display
The 505E's service panel consists of a keypad and LED display. The LED display has two 24-character lines that display operating and fault parameters in plain English. In addition, there are 30 keys that provide complete control from the front of the 505E. No additional control panel is required to operate the turbine; every turbine control function can be performed from the 505E's front panel.
Button function description
Scroll:
The large diamond button in the center of the keypad with an arrow on each of the four corners. (Scroll Left, Right) moves the display left or right within a program or run mode function block. (Scroll Up, Down) moves the display up or down within a program or run mode function block.
Select:
The Select key is used to select the variable that controls the top or bottom line of the 505E display. The @ symbol is used to indicate which line (variable) can be adjusted by the Adjust key. Only when there are changeable variables on both lines (Dynamic, Valve Calibration Modes) does the Select key and @ symbol determine which line variable can be adjusted. When only one adjustable parameter is displayed on the screen, the position of the Select key and @ symbol is not important.
ADJ (adjust):
In the Run Mode, the ““ (adjust up) moves any adjustable parameter up (larger) and the ““ (adjust down) moves any adjustable parameter down (smaller).
PRGM (Program):
When the controller is off, this key selects Program mode. In Run mode, this key selects Program Monitor mode. In Program Monitor mode, the program can be viewed but not changed.
RUN:
Initiates a turbine run or start command when the unit is ready to start.
Reset:
Resets/clears run mode alarms and shutdowns. Pressing this key also returns control to (Control Parameters/Press to Run or Program) after shutdown
Stop:
Once confirmed, initiates a controlled turbine shutdown (Run Mode). The Stop command can be disabled via the Service Mode settings (under Key Options).
0/NO:
Enters 0/NO or disable.
1/YES:
Enters 1/YES or enable.
2/ACTR (actuator):
Enters 2 or displays the actuator position (Run Mode)
3/CONT (control):
Enters 3 or displays the parameter which is in control (Run Mode); press the Scroll down arrow to display the control’s last trip cause, steam map priority,highest speed reached, and local/remote status (if used).
4/CAS (cascade):
Enters 4 or displays the cascade control information (Run Mode).
5/RMT (remote):
Enters 5 or displays the remote speed setpoint control information (Run
Mode).
7/SPEED:
Enters 7 or displays the speed control information (Run Mode).
8/AUX (auxiliary):
Enters 8 or displays the auxiliary control information (Run Mode).
9/KW (load):
Enters 9 or displays the kW/load or first stage pressure information (Run Mode).
. / EXT/ADM (extraction/admission):
Enters a decimal point or displays the extraction/admission information (Run Mode).
CLEAR:
Clears the program mode and Run mode entries and will be displayed removed from the current mode.
Input:
Enter new values in program mode and allow specific Settings to be "directly entered" in run mode
Dynamics (+ / -):
Accesses the dynamic settings of the parameters that control the actuator position in Run mode. Dynamic adjustments can be disabled via the Service Mode settings (under "Key Options"). This key also changes the sign of the entered value.
ALARM (F1):
When the key LED is on, displays the cause of any alarm condition (last/latest alarm). Press the down scroll arrow (diamond key) to display additional alarms.
OVERSPEED TEST ENABLE (F2) :
Permits the speed reference to be raised beyond the maximum controlling speed setpoint to test either the electrical or mechanical overspeed trip.
F3 (function key):
Programmable function key for enabling or disabling programmable control functions.
F4 (function key):
Programmable function key for enabling or disabling programmable control functions.
EMERGENCY SHUTDOWN BUTTON:
Large red octagonal button on the front of the enclosure. This is an Emergency Shutdown command for the control.