HIMA F3330 8-Fold Output Module
General info
Manufacture | HIMA |
Item No | F3330 |
Article number | F3330 |
Series | PLC Module |
Origin | United States(US) |
Dimension | 85*11*110(mm) |
Weight | 0.8 kg |
Customs Tariff Number | 85389091 |
Type | Output Module |
Detailed data
HIMA F3330 8-Fold Output Module
Resistive or inductive load up to 500ma (12w), lamp connection up to 4w, with integrated safety shutoff, with safety isolation, no output signal, class L disconnect - power supply requirement class ak1...6
Electrical characteristics:
Load capacity: It can drive resistive or inductive loads, and can withstand a current of up to 500 mA (power of 12 watts). For lamp connections, it can withstand a load of up to 4 watts. This enables it to meet the driving needs of many different types of loads and is suitable for equipment control in various industrial scenario
Internal voltage drop: Under a load of 500 mA, the maximum internal voltage drop is 2 volts, which means that when a large load current passes through the module, the module itself will produce a certain voltage loss, but it can still be guaranteed to be within a reasonable range to ensure the stability of the output signal.
Line resistance requirements: The maximum total acceptable line input and output resistance is 11 ohms, which has certain restrictions on the line resistance of the connection module. The influence of line resistance needs to be considered when actually wiring and connecting devices to ensure the normal operation of the module.
Application areas:
Commonly used in industries such as oil and gas, chemicals, power generation and manufacturing. The production processes in these industries have extremely high safety requirements. The high safety performance and reliable output characteristics of HIMA F3330 can meet the control requirements of these industries for key equipment and processes, ensuring the stable operation of the production process.
HIMA F3330
The module is automatically tested during operation. The main test routines are:
– Reading back of the output signals. The operating point of the 0 signal read back is ≤ 6.5 V. Up to this value the level of the 0 signal may arise in case of a fault and this will not be detected
– Switching capability of test signal and cross-talking (walking-bit test).
Outputs 500 mA, k short circuit proof
Internal voltage drop max. 2 V at 500 mA load
Admissible line resistance (in + out) max. 11 Ohm
Undervoltage tripping at ≤ 16 V
Operating point for short circuit current 0.75 ... 1.5 A
Outp. leakage current max. 350 µA
Output voltage if output is reset max. 1,5 V
Duration of the test signal max. 200 µs
Space requirement 4 TE
Operating data 5 V DC: 110 mA,24 V DC: 180 mA in add. load