GE IC698ETM001 ETHERNET MODULE

Brand:GE

Item No:IC698ETM001

Unit price:99$

Condition: Brand new and original

Quality Guarantee: 1 Year

Payment : T/T and Western Union

Delivery Time: 2-3 day

Shipping Port: China

(Please note that product prices may be adjusted based on market changes or other factors. The specific price is subject to settlement.)


Product Detail

Product Tags

General info

Manufacture GE
Item No IC698ETM001
Article number IC698ETM001
Series GE FANUC
Origin United States(US)
Dimension 180*180*30(mm)
Weight 0.8 kg
Customs Tariff Number 85389091
Type Ethernet Module

 

Detailed data

GE IC698ETM001 Ethernet Module

Product: PACSystems™ RX7i Ethernet Module with Firmware Version 1.6 IC698ETM001-BC

The Ethernet Interface module provides:
− Data exchange using Ethernet Global Data (EGD)
− TCP/IP communication services using SRTP
− Full control system programming and configuration services
− Comprehensive station management and diagnostic tools
− Two full-duplex 10BaseT/100BaseT/TX (RJ-45 Connector) ports with an internal network switch providing auto-negotiated network speed, duplex mode, and crossover detection.

Hardware Identification
The following shows the revision of the board used with this version of the RX7i Ethernet interface module.
Catalog Number Board ID
IC698ETM001-AC Carrier Card NE8A1_F2_R02
IC698ETM001-BC Ethernet EX8A1_F2_R03

Ethernet Restrictions and Open Issues
Number of SRTP Requests Tallied May Vary
When running multiple SRTP client channels, the number of requests, as reported by the client and the server, may differ between the connections.

SRTP connection remains open after IP address change
The Ethernet interface does not terminate all open SRTP connections before changing its IP address. Any existing open TCP connections are not terminated properly once the local IP address is changed. This causes SRTP connections to remain open until their underlying TCP connection times out. If faster recovery of SRTP connections is required, modify the "wkal_idle" advanced user parameter to reduce the TCP keep-alive timer to the desired maximum keep-alive time. For more information, see TCP/IP Ethernet Communications for PACSystems RX7i, GFK2224.