ABB 07KT93 GJR5251300R0101 Advant Controller Module

Brand:ABB

Item No:07KT93 GJR5251300R0101

Unit price:999$

Condition: Brand new and original

Quality Guarantee: 1 Year

Payment : T/T and Western Union

Delivery Time: 2-3 day

Shipping Port: China


Product Detail

Product Tags

General info

Manufacture ABB
Item No 07KT93
Article number GJR5251300R0101
Series PLC AC31 Automation
Origin Sweden
Dimension 73*233*212(mm)
Weight 0.5kg
Customs Tariff Number 85389091
Type
Advant Controller Module

 

Detailed data

ABB 07KT93 GJR5251300R0101 Advant Controller Module

The serial interface COM1 allows access to the AC31/CS31 basic units (07 KR 31, 07 KR 91, 07 KT 92 to 07 KT 94) as well as the communication processor 07 KP 62 of the ABB Procontic T200.

Every operating and test function of the PLC can be called up via ASCII plain text telegrams. The operating mode "Active mode" must be set on the serial interface.

Connectable units:
– Terminal in the VT100 mode
– Computer with VT100 emulation
– Computer with a program for the handling of the clear text telegrams of the operating and test functions

Interface operating mode:
The serial interface COM 1 must be set to the operating mode "Active mode" to use the operating and test functions.

RUN/STOP switch in position: STOP In switch position STOP, the PLC usually sets the operating mode "Active mode" on COM 1.

RUN/STOP switch in position: RUN In switch position RUN, the operating mode "Active mode" is set on COM 1 when one of the following two conditions is met:
– System constant KW 00,06 = 1
or
– System constant KW 00,06 = 0 and Pin 6 on COM1 has 1-signal (1-signal on Pin 6 is set by using the system cable 07 SK 90 or by not connecting Pin 6)

System behavior of the PLC
The following applies:
The processing of the PLC program has higher priority than the communication via the serial interfaces.

The PLC controls the receiving direction of the operating serial interface COM1 via interrupts. During the running PLC program cycle, the incoming characters respectively trigger an interrupt pulse, interrupting the running PLC program until the received characters are stored in the receive buffer. In order to avoid permanent interruption of program processing, the PLC controls data reception via the RTS line so that it takes place in the gap between two PLC cycles.

The PLC processes jobs received via COM1 only in the gaps between PLC program cycles. Characters are also output via COM1 only in the gaps between two program cycles. The lower the utilization of the PLC and the longer the gaps between program cycles, the higher the possible communication rate with COM1.

07KT93

ABB 07KT93 GJR5251300R0101 Advant Controller Module FAQ

What are the uses of the ABB 07KT93 GJR5251300R0101 controller module?
The ABB 07KT93 Advant controller module is part of the Advant Controller 400 (AC 400) series, which is a real-time control and automation system for industrial processes. It is often used in monitoring applications in manufacturing and electrical automation

Why does the 07KT93 module fail to start?
Power connection problem: Check whether the 24V DC power supply is connected normally and whether the power cord is damaged or loose. The module itself may also be faulty. Try replacing a new module for testing.


  • Previous:
  • Next:

  • Write your message here and send it to us